1-CHKE-R
Power cable - fire retardant, halogen-free
Construction:
1. Conductor Cu conductor of the category 1 or 2 according to IEC 60228
2. Insulation fire retardant halogen-free polymer compound
3. Cable core wrapping by PET foil
4. Bedding fire retardant halogen-free compound
5. Screening none
6. Sheath fire retardant halogen-free polymer compound
Technical parameters:
Rated voltage U0/U: 0,6/1 kV AC
Highest voltage of the Um system:
Testing voltage between cores: 4 kV AC 5 min
Testing voltage between core and screening:
Insulation resistance: > 1000 MΩ.km
Surrounding temperatures (fixed placement): - 40°C up to + 90°C
Surrounding temperatures (during installation): -5°C up to +50°C
Minimum bending radius (fixed placement): 10D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
Halogen-free, low corrosion of gasses during burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: HD 308 S2
Sheath colour: orange
The materials used do not contain any dangerous substances and fulfill the direction RoHS Nr. 2002/95/ES. The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to 60079-11.
Usage:
Halogen-free, fire retardant power cables are used in power distributions in premises where is insisted on personal protection, on the protection of equipments, constructions and materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
The construction meets the requirements of the norms of series HD 604 – special cable design for power stations. These cables are tested for service life of 40 years and the HELB accident.
The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to IEC 60079-11.
The most common derived variants:
1-CHFE-R – with screening by AlPET foil and by drain wire
1-CHFE-R /st/ - with screening by AlPET foil and by drain wire and with separate screening of AlPET foil elements and of drain wire
1-CHFOE-R /sto/ - with screening by CuSn braiding and by drain wire and with separate screening of braiding elements and of drain wire
1-CHKE-R /ZE/ - with light armour
Note: for other derived variants see the code marking of power cables.
The product is conformable with the direction EU 73/023/EEC for low voltage.
1-CXKE-R
Power cable - fire retardant, halogen-free
Construction:
1. Conductor Cu conductor of the category 1 or 2 according to IEC 60228
2. Insulation XLPE
3. Cable core wrapping by PET foil
4. Bedding fire retardant, halogen-free
5. Screening none
6. Sheath fire retardant halogen-free polymer compound
Technical parameters:
Rated voltage U0/U: 0,6/1 kV AC
Highest voltage of the Um system:
Testing voltage between cores: 4 kV AC 5 min
Testing voltage between core and screening:
Insulation resistance: > 1000 MΩ.km
Surrounding temperatures (fixed placement): - 40°C až + 90°C
Surrounding temperatures (during installation): -5°C až +50°C
Minimum bending radius (fixed placement): 10D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
Halogen-free, low corrosion of gasses during burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: HD 308 S2
Sheath colour: orange
Usage:
Fire retardant and halogen-free power cables are used in power distributions in premises where is insisted on personal protection, on the protection of equipments, constructions and of materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
The construction meets the requirements of the norms of series HD 604 – special cable design for power stations. These cables are tested for service life of 40 years and the HELB accident.
The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to 60079-11.
The most common derived variants:
1-CXFE-R – with screening by AlPET foil and by drain wire
1-CXFE-R /st/ - with screening by AlPET foil and by drain wire and with separate screening of AlPET foil elements and of drain wire
1-CXFOE-R /sto/ - with screening by CuSn braiding and by drain wire and with separate screening of braiding elements and of drain wire
1-CXKE-R /ZE/ - with light armour
CPDex PR – the variant with low heat releasing during a fire
Note: for other derived variants see the code marking of power cables.
The product is conformable with the direction EU 73/023/EEC for low voltage.