1-CHKH-V
Power cable - fireproof, halogen-free, for common installation
Construction:
1. Conductor Cu conductor of the category 1 or 2 according to IEC 60228
2. Fireproof barrier mica tape
3. Insulation fire retardant halogen-free polymer compound
4. Cable core wrapping by PET foil
5. Bedding none
6. Screening none
7. Sheath fire retardant halogen-free polymer compound
Technical parameters:
Rated voltage U0/U: 0,6/1 kV AC
Highest voltage of the Um system:
Testing voltage between cores: 4 kV AC 5 min
Testing voltage between core and screening:
Surrounding temperatures (fixed placement): - 40°C up to + 90°C
Surrounding temperatures (during installation): -5°C up to +50°C
Minimum bending radius (fixed placement): 12D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
With maintenance of insulation integrity in a fire: IEC 60331-21
Halogen-free, low corrosion of gasses during burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: HD 308 S2
Sheath colour: orange
Usage:
As a power control cable it is used in circuits ensuring the function in case of fire, especially in circuits of fire systems (e.g. extinguishing systems, emergency lighting and ventilation power supply, circuits of emergency signals and operating of firewalls).
The cables can be used everywhere that is insisted on personal protection, on the protection of equipments, constructions and of materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to IEC 60079-11.
The product is conformable with the direction EU 73/023/EEC for low voltage.
1-CXKH-V
Power cable – fireproof, halogen-free, for common installation
Construction:
1. Conductor Cu conductor of the category 1 or 2 according to IEC 60228
2. Fireproof barrier: mica tape
3. Insulation XLPE
4. Cable core wrapping by PET foil
5. Bedding none
6. Screening none
7. Sheath fire retardant halogen-free polymer compound
Technical parameters:
The rated voltage: 0,6/1 kV AC
The highest voltage of Um system:
Testing voltage between cores: 4 kV AC 5 minute
Testing voltage between core and screening: 250 V AC 1 minute
Insulation resistance: > 100 MΩ.km
Surrounding temperatures (fixed placement): -40°C up to +90°C
Surrounding temperatures (during installation): -5°C up to +50°C
Miminum bending radius (fixed placement): 12D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
With maintenance of insulation integrity in a fire: IEC 60331-21
Halogen-free, low corrosion of gasses during
burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: HD 308 S2
Sheath color: orange
Usage:
As a power control cable it is used in circuits ensuring the function in case of fire, especially in circuits of fire systems (e.g. extinguishing systems, emergency lighting and ventilation power supply, circuits of emergency signals and operating of firewalls).
The cables can be used everywhere that is insisted on personal protection, on the protection of equipments, constructions and of materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to 60079-11.
The product is conformable with the direction EU 73/023/EEC for low voltage.
up