JCXFE-V

 

Weak-current cable – screened, fireproof, halogen-free

 

Construction:

1. Conductor              Cu conductor of the category 1 according to IEC 60228

2. Fireproof barrier     mica tape

3. Insulation                fire retardant halogen-free polymer compound

4. Cable core               cores are twisted in pairs, pairs are laid up into cable core

5. Bedding                  none

6. Screening                wrapping by Al/PET foil + CuSn drain wire

7. Sheath                    fire retardant halogen-free polymer compound

             

Technical parameters:

Rated voltage:                                                                       500 V AC

Testing voltage between cores:                                 2000 V

Testing voltage between core and screening:            750 V

Insulation resistance:                                                 > 1000 MΩ.km

Surrounding temperatures (fixed placement):           - 40°C up to + 90°C

Surrounding temperatures (during installation):       -5°C up to +50°C

Minimum bending radius (fixed placement):            10D

             

Basic characteristics:             

Self-extinguishing:                                                                EN 60332-1-2

Resistant to vertical spread of flame:                                               EN 50266-2-2 category A

With maintenance of insulation integrity in a fire:               IEC 60331-23

Halogen-free, low corrosion of gasses during burning:        IEC 60754-2

Low smoke density during burning:                                     IEC 61034-2

Colour marking of cores:                                                       IEC 60189-2 edition 4 or black and white numbered couples

Sheath colour:                                                                       orange

 

Usage:

The cables can be used for signal transmission in measuring, control and safety circuits where is insisted on personal protection, on the protection of equipments, constructions and of materials (e.f. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.

Electrostatic screening ensures the protection against electrical interference.

The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to IEC 60079-11.

 

The most common derived variants:

JCXFE-V /st/ - with separately screened elements

JCXFE-V /ZE/ - with light armour

JC5XFOE-V /sto/ - with overall screening by CuSn braiding and by drain wire and with separately screened elements by braiding and by drain wire

CPDex SVF /P90-R/ – the variant with low heat releasing during a fire and with the system functionality during the period of 90 minutes (with intensified barrier against a fire)

 

Note: the element can be a core, a pair, a triad or a quad; then the standard colour marking is:

- HD 308 S2 for a core variant

- couples with black and white core – numbered

- trios with black, white and dark red core – numbered

- quads with black, white, dark red and brown - numbered

 

The product is conformable with the direction EU 73/023/EEC for low voltage.