JE-H(St)H.....(Bd)
Wiring cable – screened, fireproof, halogen-free
Construction:
1. Conductor Cu conductor of the category 1 according to IEC 60228
2. Fireproof barrier mica tape
3. Insulation fire retardant halogen-free polymer compound
4. Cable core cores are twisted into a bunch and the bunches are laid up in cable core
5. Bedding none
6. Screening wrapping by Al/PET foil + drain wire
7. Sheath fire retardant halogen-free polymer compound
Technical parameters:
Rated voltage: 230 V
Testing voltage between cores: 800 V
Testing voltage between core and screening: 800 V
Insulation resistance:
Surrounding temperatures (fixed placement): - 30°C up to + 90°C
Surrounding temperatures (during installation): -5°C up to +50°C
Minimum bending radius (fixed placement): 10D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
With maintenance of insulation integrity in a fire: IEC 60331-23
Halogen-free, low corrosion of gasses during burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: DIN VDE 0815
Sheath colour: orange
Usage:
The cable is used for fixed installation in fire signalling systems (e.g. extinguishing systems, emergency lighting and ventilation power supply, circuits of emergency signals and operating of firewalls).
The cables can be used everywhere that is insisted on personal protection, on the protection of equipments, constructions and materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
Electrostatic screening ensures the protection against electrical interference.
The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to IEC 60079-11.
The product is conformable with the direction EU 73/023/EEC for low voltage.