J-H(St)H...Bd
Installation cable - fire retardant, halogen-free
Construction:
1. Conductor Cu conductor of the category 1 according to IEC 60228
2. Insulation fire retardant halogen-free polymer compound
3. Cable core cores are twisted into quads and the quads are laid up in cable core
4. Bedding none
5. Screening wrapping by Al/PET foil + drain wire
6. Sheath fire retardant halogen-free polymer compound
Technical parameters:
Rated voltage U0/U: 230 V
Testing voltage between cores: 800 V
Testing voltage between core and screening: 800 V
Surrounding temperatures (fixed placement): - 30°C up to + 90°C
Surrounding temperatures (during installation): -5°C up to +50°C
Minimum bending radius (fixed placement): 10D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
Halogen-free, low corrosion of gasses during burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: DIN VDE 0815
Sheath colour: orange
Usage:
The cables can be used for signal transmission in measuring and control circuits where is insisted on personal protection, on the protection of equipments, constructions and of materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
Electrostatic screening ensures the protection against electrical interference.
The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to IEC 60079-11.