SCXFE-V

 

Communication cable – screened, fireproof, halogen-free

 

Construction:

1. Conductor              Cu conductor of the category 1 according to IEC 60228

2. Fireproof barrier:    mica tape

3. Insulation                XLPE

4. Cable core               cores are twisted in pairs, pairs are laid u pinto cable core

5. Bedding                  none

6. Screening                wrapping by Al/PET foil + CuSn drain wire

7. Sheath                     fire retardant halogen-free  polymer compound

             

Technical parameters:

The rated voltage:                                                     100 V

Testing voltage between cores:                                  500 V AC 1 minute

Testing voltage between core and screening:            250 V AC 1 minute

Insulation resistance:                                                 > 1000 MΩ.km

Surrounding temperatures (fixed placement):           -40°C up to +90°C

Surrounding temperatures (during installation):       -5°C up to +50°C

Miminum bending radius (fixed placement):            10D

             

Basic characteristics:

Self-extinguishing:                                                                EN 60332-1-2

Resistant to vertical spread of flame:                                                EN 50266-2-2 category A

With maintenance of insulation integrity in a fire:                IEC 60331-23

Halogen-free, low corrosion of gasses during burning:        IEC 60754-2

Low smoke density during burning:                                      IEC 61034-2

Colour marking of cores:                                                       IEC 60189-2 edition 4 or black and white numbered couples

Sheath color:                                                                          orange

 

Usage:

The cables can be used for signal transmission in measuring, control and safety circuits where is insisted on personal protection, on the protection of equipments, constructions and of materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). The cable can be used for fixed installation in fire signaling systems (e.g. circuits of emergency signals). It is possible to use them in dry or wet environment.

Electrostatic screening ensures the protection against electrical interference.

The cables can be placed in the environment with the explosion danger (zone 1, 2) providing compliances with the conditions of intrinsic safety according to IEC 60079-11.

 

The product is conformable with the direction EU 73/023/EEC for low voltage.

 